Glossary

Filtration terms, defined precisely.

Absolute efficiency
A filter's minimum guaranteed removal efficiency at a stated particle size, verified by individual scan or leak testing rather than a batch/type-test average — the basis for HEPA/ULPA classification.
Activated carbon
A porous carbon media used for gas-phase and odour filtration rather than particulate removal — contaminant molecules are captured on the carbon's internal surface (adsorption) rather than blocked by physical straining.
Air changes per hour (ACH)
The number of times a room's full air volume is replaced by supply air in one hour — a key parameter in HVAC and cleanroom design that, together with filtration stage, determines achievable particle-count classification.
Air handling unit (AHU)
The equipment that conditions and moves air through a building's ventilation system — typically housing filtration stages, heating/cooling coils, and fans — sized to the building's required airflow.
Airborne molecular contamination (AMC)
Gaseous chemical contamination — as opposed to particulate — that can affect sensitive processes such as semiconductor fabrication even when particle counts are within specification; controlled with activated-carbon or chemical-filtration media.
Airflow
The volume of air moving through a filter or system per unit time, typically expressed in m3/h or CFM — a filter's rated airflow determines the pressure drop and efficiency it will actually deliver in service.
Arrestance
A coarse-particle removal efficiency measure (used for pre-filters, tested against a synthetic dust) expressed as the percentage of dust mass captured — distinct from the finer-particle efficiency measures used for fine and HEPA filters.
Bag filter
A filter using fabric bags rather than pleated panels — used both as an extended-surface air filter (see pocket filter) and, in a different construction, as the filtering element in industrial dust collectors.
Cartridge filter
A self-contained, typically cylindrical or pleated filter element used across compressed-air, hydraulic, liquid-process, and dust-collection duties — sized by flow rate and required retention/efficiency rating.
Cleanroom classification
A room's permitted airborne particle concentration at specified particle sizes, defined by standards such as ISO 14644 — the classification drives the required filtration stage, airflow, and air-change rate.
Coalescing filter
A filter that merges (coalesces) small liquid droplets suspended in a gas or another liquid into larger droplets that can then separate out by gravity or a downstream separator stage — used in compressed air, fuel, and gas systems.
Compressed air filtration
Filtration of compressed-air systems to remove oil carryover, moisture, and particulate before the air reaches pneumatic tools, instrumentation, or process equipment.
Deep pleat
A pleat construction using wider, deeper pleats with full-height separators, giving a large media area and low pressure drop — the traditional HEPA filter construction.
Differential pressure
The pressure difference across a filter (or between rooms/zones), monitored to track filter loading over service life or to confirm a required room-pressurisation cascade.
Dust collector
A system (bag-house or cartridge-type) that captures airborne dust from an industrial process before the air is exhausted or recirculated — sized by required airflow and the dust's characteristics.
Dust holding capacity
The total mass of dust a filter can capture over its service life before reaching its final (change-out) pressure drop — a key factor in expected media life under a given dust loading.
EN 1822
The European standard defining HEPA and EPA filter efficiency classes (E10–U17) based on efficiency at the most penetrating particle size (MPPS).
Face velocity
Airflow divided by the filter's face area — expressed as m/s or fpm — a key sizing parameter since efficiency and pressure drop both depend on how fast air moves through a given media area, not just total airflow.
Filter frame
The structural housing that holds filter media in place and interfaces with the installation — commonly galvanised steel, aluminium, or moulded plastic, chosen for strength, weight, corrosion resistance, and sealing method.
Filter media
The material that actually captures particulate — glass fibre, synthetic fibre, or other engineered materials — selected for the target efficiency grade, airflow, and operating environment.
Fine filter
An intermediate filtration stage, finer than a pre-filter but below HEPA grade, typically the last stage before terminal filtration or the final stage in general ventilation systems not requiring HEPA.
Fuel-water separator
A filtration device that removes entrained water and solid contamination from fuel, protecting downstream engines or turbines from water-related damage and combustion issues.
Gasket
A sealing material fitted to a filter frame's perimeter, preventing unfiltered air from bypassing the media at the housing interface — critical for HEPA and other high-efficiency installations where any bypass defeats the filter's rated performance.
HEPA
High Efficiency Particulate Air filter — a filter class defined by a minimum particle-removal efficiency, commonly at least 99.95% or 99.97% depending on the classification standard used.
Hydraulic filtration
Filtration of hydraulic fluid to a target cleanliness level (often expressed per ISO 4406) to protect pumps, valves, and actuators from wear caused by particulate contamination.
ISO 16890
An international standard for classifying general ventilation air filters by their efficiency against PM1, PM2.5, and PM10 particle size fractions, replacing the older EN 779 classification in many markets.
Laminar flow
Air movement in parallel, non-mixing layers (as opposed to turbulent flow) — used in cleanroom and critical-environment design to sweep particulate away from a work zone in a predictable, unidirectional pattern.
Leak test (scan test)
A post-installation verification method — typically using a DOP or PAO aerosol challenge and a photometer scan — confirming a HEPA/ULPA filter and its seal are free of leaks that would bypass the rated efficiency.
MERV
Minimum Efficiency Reporting Value — a North American filter efficiency classification (1–16 or higher for HEPA-grade) defined by ASHRAE 52.2, commonly cross-referenced against ISO 16890 and EN 779 classes.
MPPS
Most Penetrating Particle Size — the particle size at which a given filter media is least efficient, used as the reference point for HEPA/ULPA efficiency testing because it represents the worst-case performance.
Media pack
The assembled block of pleated (or otherwise formed) filter media inside a frame — the core filtration element, distinct from the frame that houses it.
Micron
A micrometre (one-millionth of a metre) — the standard unit for describing particle size and filter retention rating in filtration.
Mini pleat
A pleat construction using closely-spaced, shallow pleats (often with hot-melt adhesive spacers instead of full separators) to pack more media area into a compact, lightweight filter — common in HEPA applications with limited installation depth.
Nominal efficiency
A filter's stated removal efficiency at a specific particle size under standard test conditions — describes typical performance rather than a guaranteed minimum for every unit.
Overspray
Paint or coating particulate that does not land on the target surface during spraying — captured by arrestor media in the booth's exhaust path to protect equipment and meet discharge requirements.
Paint arrestor
Filter media (commonly glass fibre or synthetic pads) designed to capture paint overspray in a spray booth's exhaust path, sized to the booth's airflow and the coating's solids content.
Particulate matter (PM)
Airborne particles classified by size — PM10 (10 microns and below) and PM2.5 (2.5 microns and below) are the size fractions referenced by ISO 16890 and most air-quality standards.
Pleat
A fold in the filter media that increases the usable surface area within a given frame size, reducing face velocity through the media and lowering pressure drop at a given airflow and efficiency grade.
Pocket filter
An extended-surface filter constructed as fabric pockets or bags, giving a larger media area (and therefore lower pressure drop) than an equivalent flat panel at the same efficiency grade.
Pre-filter
The first, coarsest filtration stage in a system, capturing larger particulate to protect and extend the service life of finer downstream stages.
Pressure drop
The reduction in air (or fluid) pressure as it passes through a filter, caused by resistance from the media and construction — reported as initial (clean) and final (recommended change-out) resistance.
Separator
A corrugated spacer (traditionally aluminium, sometimes hot-melt or thermoplastic in newer construction) placed between pleats to hold them apart, maintaining airflow paths through deep-pleat HEPA and similar high-efficiency filters.
Service life
The expected operating period of a filter before it reaches its final (change-out) pressure drop or efficiency degrades below requirement — depends on dust holding capacity, dust loading, and airflow.
ULPA
Ultra Low Penetration Air filter — a class above HEPA, typically rated at 99.999% or higher removal efficiency at the most penetrating particle size, used in the most particle-sensitive cleanroom applications.
V-bank filter
A filter constructed with media panels arranged in a V-shaped (or W-shaped) configuration to fit a large media area into a compact housing footprint, commonly used for high-airflow HEPA and fine-filtration duties.
VOC (Volatile Organic Compound)
A class of chemical compounds that evaporate readily at room temperature, commonly generated by coatings, solvents, and adhesives — a typical target contaminant for activated-carbon and other gas-phase filtration.